Inner Range are world leaders in the design and manufacture of state of the art security solutions. Consultants who specify their products, technicians who install them and consumers who use them all benefit on a daily basis from the pursuit of excellence that is the hallmark of Inner Range System Design.


Concept 4000 Hardware Platform
Concept 4000 is a modular integrated hardware platform offering you an expandable, flexible and highly secure Access Control, Security/Intruder detection and Automation package.
The Concept 4000 Control Module delivers unrivalled security power with its integrated combination of intruder alarm, access control, building automation and security communications features. The flexible, modular design of the Concept 4000 architecture allows the expansion of a single control module to a network of hundreds of modules, 50,000 users, 2000 inputs, thousands of outputs, 250 areas and 250 doors. The Control Module comes with 16 zone inputs, 2 outputs, an on board switch mode power supply, LAN port, modem, serial port, siren and relay outputs.
Expansion boards can add an extra eight outputs directly to the Control Module. Further expansion and functionality is realised with the addition of expansion modules which are connected to the Concept 4000 Control Module using a secure, encrypted RS485 LAN.
|
Physical Specifications |
||
|
|
||
|
Cabinet Dimensions |
460(L) x 358(W) x 85(D) (mm) | |
|
|
|
|
|
PCB Dimensions |
200(L) x 200(W) x 45(D) (mm) (Inc. heat sink) | |
|
|
|
|
|
Weight |
9.5Kg (in Medium Low Profile Enclosure) | |
|
|
|
|
|
Installation Environment |
0°C - 40°C @15% - 85% Relative humidity (non-condensing) | |
|
|
|
|
|
Cabinet Battery Bracket |
To suit 12V 7AH Sealed Lead Acid battery | |
|
|
||
|
|
||
|
Electrical |
Plug Pack and PCB Versions | Transformer Versions |
|
|
||
| Mains Input Voltage | 240VAC 50Hz | 240VAC 50Hz |
|
|
|
|
| Mains Input Current | 100mA | 500mA |
|
|
|
|
| Input Voltage to PCB | 16-18VAC | 16-18VAC |
|
|
|
|
|
Fuse Protection |
Separate fuses for battery, Siren 1, Siren 2, LAN & Detector Power |
|
|
|
||
|
|
||
| Current Consumption | ||
|
|
||
| Total Current Limit |
1.3A |
2.2A |
|
|
|
|
|
Operational Current (No peripherals connected) |
275mA |
275mA |
|
|
|
|
|
Recommended current allowance for battery charging |
300mA |
300mA |
|
|
|
|
|
Available Current (for detectors, auxiliaries, relays, etc) |
700mA |
1.2A |
|
|
||
|
|
||
|
Inputs |
||
|
|
||
|
Zone Inputs |
16 |
|
|
|
|
|
|
Cabinet Tamper Input |
Yes |
|
|
|
||
|
|
||
|
Outputs |
||
|
|
||
|
Siren Outputs |
2 (Max load: 2 x 8 Ohm, 10 Watt siren speakers) | |
|
|
|
|
|
Outputs (Open Collector) |
2 (Expandable to 10 using the 8 Auxiliary Expander Board) |
|
|
|
|
|
|
Relays |
Expandable to 8 with optional Passive Relay board (replaces Auxiliaries 3-10) |
|
|
|
||
Connectivity:
The control module is the heart of a Concept 4000 system.

Inner Range Concept 4000 Contol Module options:
Inner Range Concept 4000 Module: